- Home
- Surge Protection
- CENTECH Surge Protector- 385V Type 2-2+3 poles- 230V IT/TT
- Product Information
- Technical Descriptions
- Questions and Answers
- Documentation
- Warranty
Product Information
- Especially Adapted for 230V IT/TT net
- Surge protection type 2 (intermediate protection)
- For installations with/ without distributed earth and with signal contact
- No requirement for additional protection (ground fault circuit breaker/non- flammable enclosure)
Surge protection (etc.) from CENTECH can be used in all types of installations for the distribution of power. It is intended for mounting on a DIN- Rail and fits under a modular cover. Type 2+3 surge protector is especially developed for protection against overvoltage in low-voltage systems. Most have replaceable protection modules. Enclosures are halogen-free. Manufactured from flame retardant PBT or fire resistant nylon (depending on the model). All terminals are made of copper, if it should be connected with aluminum, transitions must be used.
The surge protector is supplied (internally) with a signal contact for indicating the fuse.
Can be used on installations with or without distributed soil.
From 1 January 2019, a surge protector is a legally required protection in the fuse box when installing a new current course to the charging of electrical vehicles. This applies both to a new charging point or charging station.
According to regulations on electrical equipment §21, we are obliged to inform our customers that all electrical equipment intended to be part of a fixed electrical installation can only be installed by authorized and registered installation company installasjonsvirksomhet.
Technical Details
Area of Use | Indoors in fuse box |
---|---|
Power Grid | IT / TT |
Rated Voltage | 385V (AC) / 505 (DC) |
Number of Poles | 2- and 3-poles |
Type | 2+3 (Intermediate protection) |
Nominal Discharge Impulse Current (8/20) Imax | 20 kA |
Maximum Arrester Surge Current (8/20) Imax | 40kA |
Security Level/ Up @ In | <2.0kV |
Reaction Time | ≤100 ns |
Follow Current/ Leakage Current | No |
Largest Pre-Connected Fuse | 125A |
Overvoltage Resistance | 700V/120min |
Operating Temperature | - 40ºC - + 80ºC |
Conductor Cross Section | Single core 4-35mm². Multi-wired with end sleeve 4-25mm² |
Operating Temperature | -30°C to +50°C |
Installing | 35mm DIN, according to EN 50022/DIN46277-3 |
Enclosure Material | Thermoplastic, UL94 V-0. Self-extinguishing. |
Protection Class (IP) | IP20 |
Installation Width | 2 modules, DIN 43880 |
Thermal Disconnect (internal solder fuse) | Indication flag window: Green = normal, Red = fault, replace plug. |
Signal Contact | Yes |
Signal Contact Type | Potential-free contact set NO/NC |
Nominal Voltage/Current Out/In | AC: 250V/0.5A DC: 250V/0.1A; 125V/0.2A; 75V/0.5A |
Largest Cross-Section Signal Contact |
Max 1.5 mm² (or # 16AWG) |
Sales Packaging | 1 pc |
Volume | 0,194 dm³ (2-poles) 0,292 dm³ (3-poles) |
Packaging Measurements | 90 x 36 x 60 mm (2-poles) 90 x 54 x 60 mm (3-poles) |
Weight | 100g (2-poles) 130g (3-poles) |
Standards and Approval |
IEC61643-11:2011; UL1449 4th |
Warranty | 2 years |
Questions and Answers
Do I have to have surge protection?
NEK 400:2018, part standard 722 supply of electrical vehicles states the following:
It is now required that the protection point must be protected by a surge protector. This can preferably be a surge protector that stands in front of the entire installation.
The reason being is that there is a greater increase in the number of rechargeable cars that have been destroyed as a result of lightning surges or connection surges. The repair costs can reach several hundred thousand kroner and it is not certain that this is covered by insurance. It is recommended to interrupt and disconnect the charging equipment during thunderstorms.
Warranty
We are proud of our products and it is important for us that you, as a customer, are satisfied. That's why we give you a 2 year warranty on the vast majority of our products- with the exception of consumer goods. Look for the warranty logo to see what applies to this particular product. Our warranty means that this product should function as expected through it's entire warranty time. (In addition to your rights under the Consumer Goods Act). Read more about this warranty in our purchase conditions kjøpsbetingelser.
God nettside, god betalingsløsning, rask forsendelse.
Er veldig fornøyd med både prisen på overspenningsvernet og installasjonen av dette. Det var samme pris som for 1 fas overspenningsvern og siden det var 3-fas så kunne det monteres i sikringsskapet slik at det er over spennings værn for hele installasjonen der vi bor.
Related Products
SKU: 1631861
AVAILABILITY: In stock
PRODUCT TYPE: Surge protection
VENDOR: GARO
Product Information Produktinformasjon Spesielt tilpasset for 400V TN-nettverk Type 2 overspenningsbeskyttelse (sekundærbeskyttelse) For systemer med eller uten distribuert jording Ingen krav til ekstra beskyttelse (jordfeilbryter/ikke brennbart kapsling) GARO's Surge Protection Device (SPD) can be used in all types of power...
1.383 kr eks. mva.
SKU: 1631863
AVAILABILITY: In stock
PRODUCT TYPE: Surge protection
VENDOR: GARO
Product Information Product Information Especially adapted for 230V IT/TT networks Type 2 surge protection (intermediate protection) For systems with or without distributed ground No requirement for additional protection (ground fault circuit interrupter/non-flammable enclosure) Surge protection (SPD) from GARO can be...
1.383 kr eks. mva.
SKU: CV067300
AVAILABILITY: In stock
PRODUCT TYPE: Surge protection
VENDOR: CENTECH
Product Information Product Information Especially Adapted for 400V TN-grid Surge Protection Type 2 (intermediate protection) Installs on a DIN-Rail Especially developed against overvoltage in low voltage systems Surge protection (etc.) from CENTECH can be used in all types...
639 kr eks. mva.